mcr WIP Mercor

mcr WIP/T, mcr WIP/T-G - multi-blade transfer fire damper

Fire resistance class: EI160, EI2120 and EI 120 (ve i↔o) / E120 (ve i↔o)

Technical Approval AT-15-9582/2015.

Certificate of constancy of performance 1396-CPR-0097.

Dampers are classified as per EN 13501-2 and tested according to EN 1366-2.

Dampers certified for conformance with EN 15650.

Dampers are classified as per EN 13501-3 and tested according to EN 1366-2.

Declaration of performance 001-05-CPR-2015.

Optional EX making of dampers (as per ATEX directive) for applications in explosion hazard zones.

KDB ATEX 17.0616, EU Declaration of conformity 001-01-2017.

Transfer and relieving dampers of fire resistance independent from direction of air flow and installation side.

Fixed, narrow damper thickness, regardless of B x H dimensions.

 

mcr WIP/T transfer dampers and mcr WIP/T-G pressure-relief dampers are designed for installation in fire and comfort ventilation systems. They are installed in fire partitions, without connecting ventilation ducts to them; they preserve fire resistance of building partitions during fire.

 

mcr WIP/T dampers are used as transfer dampers. They feature mechanisms with thermoelectric activators or without activators, depending on the function.

 

mcr WIP/T-G dampers are used as pressure-relieving dampers, e.g. in gas extinguishing systems. This variant features mechanisms without thermoelectric activators.

When made for potentially explosive zones (EX variant), the dampers may operate in zone 1 (risk of explosion of gases inside and outside of ventilation ducts) and zone 21 (risk of explosion of dust outside ducts). The dampers conform to the requirements of group II category 2G and -/2D.

  • small thickness of damper – 140 mm
  • cut-off barrier does not protrude outside the damper body, regardless of damper dimensions
  • large active damper in the multi-plane dampers segment
  • possibility of using in gas extinguishing systems
  • optional making in EX variant
  • operating reliability up to 10 000 cycles

Dimensions for rectangular dampers:

  • nominal width from 120 to 1000 mm
  • nominal height from 160 to 1000 mm
  • maximum area of section of single damper not larger than 1 m2

Apart from standard dimensions, dampers can be customized to any size within the specified ranges.

 

Control:

  • Belimo type mechanism – actuators family with return spring and thermoelectric trigger (BF, BFL, BFN, EXBF series)
  • Belimo type mechanism – actuators family without return spring, without thermoelectric trigger (BE, BLE series)

Detailed technical data are contained in the technical catalogue.

Making variants:

  • mcr WIP/T [BF…-T, BFL…-T, BFN...-T, EXBF] - fire transfer damper for ventilation ducts with electric actuator with return spring and thermoelectric trigger - damper shutting and opening using actuator
  • mcr WIP/T [BF…, BFL…, BFN…, EXBF] -  fire transfer damper with electrical actuator with return spring - damper opening and shutting using actuator
  • mcr WIP/T [BE, BLE]– transfer fire damper with actuator without return spring - damper opening and shutting using actuator

Additional equipment:

  • MSTx1 – single duct cover (RAL 9010 as standard)
  • MSTx2 – double duct cover (RAL 9010 as standard)

Duct cover can be painted to any RAL color.